180 kVA – 250 kVA

Features
  • Low OPEX:Best in class fuel efficiency with O2E technology
  • Robust and Reliable Product:Lowest maintenance and trouble free product with Kirloskar Liquid Cooled Engines
  • Start Type:Controller Based Easy Push Start Type
  • Customer Service:Quick and affordable door step service coverage (420+ service touch points and 6000+ KOEL trained service professionals on field)
  • Warranty:2 years warranty & labour free onsite service under warranty period
  • KRM:Critical genset parameters can be views on laptop or mobile

Description

KOEL GREEN is the market leader and India’s #1 Genset Brand. KOEL’s customised power solutions suit a wide range of 04applications, meeting prime power requirements. KOEL GREEN Gensets are available in sound resistant and environment friendly canopies. KOEL GREEN high horse power (HHP) range is spearheaded by SL90 and DV series. Upgraded with carefully selected technologies to meet latest CPCB emission norms, both SL90 and DV series Gensets are the most efficient machines delivering clean power to large requirements. Having best-in-class fuel economy, the performance capabilities are further enhanced with best-in- class block loading. KOEL Green HHP Gensets are extensively used in a variety of applications ranging from standard stand-alone Gensets to auto synchronized Gensets, special applications like Stone Crusher to Heat Exchanger cooled solutions for basement installations. KOEL Green is celebrating 30,000 HHP Genset sales, a testimony of superlative product performance in most demanding applications and customer’s trust in the range.

Best-in-class Fuel Efficiency10

KOEL Green Gensets offer a unique combination of CPCB norm compliance and enhanced fuel efficiency. Across the range, KOEL Green Gensets offer substan&al savings in fuel cost.

O2E Series (Opmal Operang Efficiency):

Genset ratings are selected based on the present load and future expansion. Fuel efficiency of most Gensets is optimized at the full rating of the Genset.

In practice, Gensets rarely get loaded to full capacity. Power demand varia&tions across day & night, weekdays & weekends.

Summer & winter lead to an average 50-70% loading on the gensets.

Considering this practical situation, KOEL has extended fuel efficiency optimization from 100%, right up to 50% of rated load. Combination of best-in-class fuel efficiency & O2E provides a double advantage.

Best-in-class Fuel Efficiency

KOEL Green Gensets offer a unique combination of CPCB norm compliance and enhanced fuel efficiency. Across the range, KOEL Green Gensets offer substan&al savings in fuel cost.

O2E Series (Opmal Operang Efficiency):

Genset ratings are selected based on the present load and future expansion. Fuel efficiency of most Gensets is optimized at the full rating of the Genset.

In practice, Gensets rarely get loaded to full capacity. Power demand varia&tions across day & night, weekdays & weekends.

Summer & winter lead to an average 50-70% loading on the gensets.

Considering this practical situation, KOEL has extended fuel efficiency optimization from 100%, right up to 50% of rated load. Combination of best-in-class fuel efficiency & O2E provides a double advantage.

Controls at your finger- tips11

There is no comfort like being in command. KOEL Green Gensets put the command in your hands. Micro-processor based Genset controllers display a host of Genset parameters and put all controls at your fingertips.

Monitoring Features
  • Lube oil Pressure, Engine Temperature, RPM, lube oil Temperature*
  • Run Hours, No. of starts, Fuel Level, Auto / Manual Stop, BaMery charge condition, AC Phase Voltage, Current, kVA, kW, kWh, kVAr, Power Factor
Optional Features
  • Modbus communica&on*
  • * Features are available from 15 kVA onwards

Diagnostic Features
  • Ballery charging failure, Over speed, Under speed, Over Current, Under Voltage, Over Voltage, Over kW, Phase Sequence monitoring, Phase missing, Common Alarm, Hooter output
  • Low lube oil Pressure, High Engine Temperature, Low/High battery voltage, Low Fuel Level alarm, Over Crank protection, Routine Maintenance indicator, Genset Test Facility, fail to start/stop

Peace-of-mind Ownership12

KOEL Green Gensets have always been preferred for their robust design and reliability over long usage life.

KOEL Green range carries the confidence of well-established and proven engine platforms. For compliance to revised CPCB norms, KOEL has carefully selected those technologies which not only retain, but enhance Gensets durability and on-site serviceability.

Thus, KOEL Gensets offer you many years of trouble-free performance; backed by the assurance of prompt support. Peace-of-mind driven by product reliability and low cost of ownership.

7-Days assured Delivery09

KOEL Chhota Chilli Gensets comes with a promise of assured delivery within 7 days of confirm order placement. Genset being a high value capital purchase may lead to needless block of capital and hence need not be purchased in advance. It is prudent to order the genset at the right time and plan the deliveries in line with your readiness to use. This will also avoid damages to genset due to lying unattended at site and engine re-validation cost.

Product Specifications

Prime Rating at rated rpm ( as per ISO8528)1

kVA 160 180 200 250
kW 128 144 160 200

Genset Model

  KG1-160WS KG1-180WS KG1-200WS KG1-1-250WS

Frequency

Hz 50 50 50 50

Power factor

lagging 0.8 0.8 0.8 0.8

Voltage

V 415 3Ø 415 3Ø 415 3Ø 415 3Ø

Governing class (As per ISO 8528 Part-V)

G3 G3 G3 G3

Noise level

dBA < 75 < 75 < 75 < 75

Fuel Consumption*

At 100% Load Ltrs/hr 36.6 41.3 45.9 56.9
At 75% Load 27.7 30.9 34.4 42.6
At 50% Load 19.1 22.7 25.5 22.9

Fuel tank capacity

Ltrs 300 460 460 460

Weight of genset with canopy (approx..)^

Dry Kg 2730 3900 3900 4010
Wet Kg 3010 4300 4340 4320

Overall dimensions of genset^

Length mm 4000 4300 4340 4340
Width mm 1500 1740 1740 1740
Height mm 1915 1970 1970 1975

Electrical Battery starting voltage

Volts-DC 12 24 24 24
ENGINE

Engine Model

6K1080TA G2 GSL1500TA G2 GSL1500TA G2 GSL1500TA G3

Rated output (Prime Continuous rating as per ISO 8528-1)

KW 147 183 183 228
HP 200 248 248 310

No. of cylinder

Number 6 6 6 6

Cubic capacity

Ltrs 6.48 8.86 8.86 8.86

Bore x Stroke

mm 150 x 125 118 x 135 118 x 135 118 x 135

Rated Speed

RPM 1500 1500 1500 1500

Aspiration

NA/TC/TA TA TA TA TA

Lube Oil change period

Hrs 500 500 500 500

Lube Oil Sump Capacity

Ltrs 18 27 27 27

Coolant Capacity

Ltrs 28 32 29.2 31.8

ALTERNATOR

Insulation Class

Class H

Ingression Protection

IP 23

Alternator Efficiency (at 100% load) 0.8 pf**

93 93 93.5 93.6

Alternator Efficiency (at   75% load) 0.8 pf**

93.3 93.6 93.8 93.9

Permissible Voltage Dip at Full Load 0.8 pf

< 20% < 20% < 20% < 19%

Time Permitted to build up rated voltage at Rated RPM

< 1 sec provided engine reach the rated speed

Short Circuit Ratio

0.518 0.53 0.545 0.45

Short Circuit Withstand Time

sec 3 times rated current for < 3sec

Overload Withstand Capacity

% 10% overload for one hour once in 12 hours & for 150% for 30 sec